阳光凯迪新能源集团有限公司SunShineKaiDiNewEnergyGroupCo.,Ltd电厂运行巡回检查管理规定编号:KDKG/PF-107版本:A/02011年10月15日发布2011年10月15日实施阳光凯迪新能源集团有限公司发布
目录1目的··········································································································12范围··········································································································13定义··········································································································14职责··········································································································15程序··········································································································巡回检查的分类.......................................................................................................................................巡回检查路线...........................................................................................................................................巡回检查工作的要求...............................................................................................................................巡检周期...................................................................................................................................................46相关文件·······································································································47记录··········································································································4
1电厂运行巡回检查管理规定版次:A/0页次:/41目的为了保证阳光凯迪新能源集团公司各电厂设备长周期运行,加强设备巡回检查管理,不断提高设备健康水平,特制订本规定。2范围本规定适用于阳光凯迪新能源集团公司已投产的各电厂(以下简称“电厂”)设备巡回检查的管理工作。3定义巡回检查是发现缺陷,处理缺陷,确保设备安全经济运行的必要手段,运行人员必须按检查项目、内容及时间、路线、次数、频次对所辖设备进行检查,并对检查的质量负责。4职责集团公司安全生产技术中心生产技术部是各电厂安全生产技术归口管理部门,具有“两票三制”的监督、检查和考核职能。电厂生产副总应随时掌握巡回检查制度的具体执行情况。发电维护部负责制定《设备巡回检查管理实施细则》,并对实施细则落实情况进行检查与考核。各专业专工负责检查本专业设备的定时巡检执行情况及巡检记录。各岗位运行人员负责本制度和电厂《设备巡回检查管理实施细则》的具体落实,并确保落实效果。5程序巡回检查的分类定时巡回检查:指运行人员按照规定的路线和时间所进行的接班和班中检查。接班检查在正点接班前30分钟开始;班中检查应每两小时巡检一次。重点检查:是针对设备特点和运行方式、负荷情况、自然条件变化等所增加次数的检查。即时检查:当运行人员根据经验判断认为设备异常运行时,立即到现场对设备进行的检查。规定检查:对特殊岗位规定的检查。本文件为阳光凯迪新能源集团有限公司版权所有未经许可不得影印
2电厂运行巡回检查管理规定版次:A/0页次:/巡回检查路线电气专业巡回检查路线二次设备保护间→发电机→发电机出线间、励磁间→室外变电站→110KV(或35KV)出线PT→400V配电室→10KV配电室→炉侧转机→机侧MCC、转机→综合水泵房配电室、转机→输料机MCC→给料机MCC→除灰输渣机控制柜、转机→雨水泵房MCC、转机→空压机控制柜→布袋除尘器配电柜。锅炉专业巡回检查路线集控室→一、二次风管道、风门→火检系统、减温水系统→水冷壁、省煤器、空气预热器、吹灰器、烟风道、过热器、汽包→给料机平台→一二次风机、引风机、返料风机→除灰输渣设备→疏水箱、疏水泵→空压机房→零米汽、气、水、管道。汽机专业巡回检查路线集控室→除氧器→主汽门→高压调门→发电机转子→射水抽汽器→排烟风机→主油箱→后汽缸喷水电磁阀→高加保护电磁阀→轴封加热器→#1低加→凝汽器热水井补水→抽汽逆止阀控→轴封供汽→本体疏水扩容器→胶球清洗系统→水坑排污泵→凝汽器→冷油器→油净化装置→油泵→凝结水泵→射水箱→射水泵→#2给水泵组→#1给水泵组→#2低加→#1高加→#2高加→综合水泵房→机力冷却塔→循环水泵进水间滤网→循环水泵→集控室。化学巡回检查路线水处理值班室→零米水处理转机→清洗水箱→中间水箱→阴阳混床→﹟1、﹟2多介质→除盐水箱→废水池、转机→汽水在线分析室→酸碱计量装置→油、燃料分析室→厂区深井泵→综合水泵房循环水加药间。各电厂根据各自的实际情况在此基础上完善相应的巡检路线。巡回检查工作的要求巡回检查人员在检查设备时应严肃认真,思想集中,带全检查工具(听针、手电、测振表、测温仪、对讲机等),采取眼看、耳听、鼻闻、手摸等方法正确判断并及时发现设备隐患。在巡检时必须遵守《电力安全工作规程》。检查人员在危险区域接近危险部位(如高温、高压、有毒气体、高电压设备等)检查时,应严格执行有关规程规定的安全事项,禁止长时间停留。检查人员应了解设备的特性及与系统的关系,了解设备正常时的温度、振动和声音,熟知阀门和挡板在不同负荷时的开度、仪表指示在不同负荷时的相应位置。检查时,按规定做好记录,若发现设备有异常及疑问,应加强监视,分析原因,本文件为阳光凯迪新能源集团有限公司版权所有未经许可不得影印
3电厂运行巡回检查管理规定版次:A/0页次:/4并及时向值长汇报,并按值长批示处理。在紧急情况下,可以先按规程处理后再汇报。如发现设备缺陷,应认真分析并采取有效措施防止扩大,遇有疑难问题难以处理应及时向有关领导汇报。副值外出巡检应得到主值的许可,途中应向主值汇报到达的地点和检查的情况;主值外出巡检应得到值长的许可,途中应向值长汇报到达的地点和检查的情况;特别是进入和离开危险区域时更要汇报,以便及时掌握巡检人员的情况。巡检中发现的异常及所作的异常处理必须在交、接班时交待清楚,并做好详细记录,接班人员在接班前要进行确认。设备或系统停后检修时,巡检人员应了解检修进度,若发现安全措施有变动,安全标示牌不齐全,检修部分与运行设备有关的系统隔绝不可靠时,应立即通知检修停止工作,收回工作票,并汇报有关领导。值长巡视或检查设备时,应向主值说明去向。值长和电气主值不得同时离开集控室。主值巡视和检查设备时,应向值长汇报,并向副值说明去向。遇有下列情况时,值长应安排增加巡检次数及重点检查部位:新安装或大修后初次投入试运行的设备。存在缺陷的运行设备。发生过故障的同类设备。带病异常运行设备。受系统故障影响的设备。启停频繁的设备。大雪、大雾、雷雨后和天气骤然变化时的室外电气设备。值长认为有必要检查的设备。设备改造或大修后72小时内。设备小修后24小时内。事故处理后8小时内。设备在粉尘、高温、强酸碱、蒸汽、潮湿、原水质恶化等恶劣条件下。特殊巡视检查的设备、内容、周期、路线由发电维护部、值长自行制定。机组发生故障时,巡检中的检查人员应立即返回集控室参加事故处理。本文件为阳光凯迪新能源集团有限公司版权所有未经许可不得影印
4电厂运行巡回检查管理规定版次:A/0页次:/巡检周期当值期间运行人员按规定对设备进行定期全面检查;夏季时期应对主要设备及重要辅机加强检查;对带病设备在停运检修前也应加强检查,值长每班对主要设备系统至少检查一次。6相关文件国家电网公司《电力安全工作规程》电厂《运行规程》《生产技术管理程序》KDKG/PF-2007记录无本文件为阳光凯迪新能源集团有限公司版权所有未经许可不得影印